1. Regulations on layout of diesel generator room
	 
		 
		The diesel generator room can be arranged on the first floor or the 
underground floor, and shall meet the following requirements:
	 
		 
		1.1 The diesel generator room shall be separated from other parts by 
partitions with a fire resistance limit of not less than 2.00h and floors with a 
fire resistance limit of 1.50h.
	 
		 
		1.2 The oil storage room shall be set separately, the oil storage capacity 
shall not exceed the required amount for 8 hours, and anti leakage and anti oil 
leakage measures shall be taken. The oil tank shall be equipped with vent pipe 
(outdoor); The oil storage room shall be separated from the generator by 
firewall; When the door must be opened on the firewall, a class a fire door that 
can close automatically shall be set.
	 
		 
		1.3 Adopt independent fire separation and separate fire compartment.
	 
		 
		2. Provisions on allocation of fire-fighting facilities
	 
		 
		2.1 There are fire hydrants, fire hoses and fire water guns outside the 
machine room.
	 
		 
		2.2 The machine room is equipped with oil fire extinguishers, dry powder 
fire extinguishers and gas fire extinguishers.
	 
		 
		2.3 There are eye-catching no fireworks safety icons and no fireworks 
words.
	 
		 
		2.4 The machine room is equipped with a dry fire sand basin.
	 
		 
		2.5 Isolation measures shall be taken with the oil depot.
	 
		 
		2.6 The generator set shall be at least one meter away from buildings and 
other equipment, and good ventilation shall be maintained.
	 
		 
		2.7 There are emergency lighting, emergency instructions, and independent 
ventilation in the basement. Fire alarm device.
	
	
	
	
	
	
	
	
	
	
	
	
	
 