1. Regulations on layout of diesel generator room
The diesel generator room can be arranged on the first floor or the
underground floor, and shall meet the following requirements:
1.1 The diesel generator room shall be separated from other parts by
partitions with a fire resistance limit of not less than 2.00h and floors with a
fire resistance limit of 1.50h.
1.2 The oil storage room shall be set separately, the oil storage capacity
shall not exceed the required amount for 8 hours, and anti leakage and anti oil
leakage measures shall be taken. The oil tank shall be equipped with vent pipe
(outdoor); The oil storage room shall be separated from the generator by
firewall; When the door must be opened on the firewall, a class a fire door that
can close automatically shall be set.
1.3 Adopt independent fire separation and separate fire compartment.
2. Provisions on allocation of fire-fighting facilities
2.1 There are fire hydrants, fire hoses and fire water guns outside the
machine room.
2.2 The machine room is equipped with oil fire extinguishers, dry powder
fire extinguishers and gas fire extinguishers.
2.3 There are eye-catching no fireworks safety icons and no fireworks
words.
2.4 The machine room is equipped with a dry fire sand basin.
2.5 Isolation measures shall be taken with the oil depot.
2.6 The generator set shall be at least one meter away from buildings and
other equipment, and good ventilation shall be maintained.
2.7 There are emergency lighting, emergency instructions, and independent
ventilation in the basement. Fire alarm device.